IceCubeUpgradeWinterHeatingRequirements_20201216.pdf
Handle: v_Document-89676
Owner: Feyzi, Farshid (User-1923, ffeyzi:LDAP)DS
Friday, October 15, 2021 02:02:05 PM CDT
Friday, October 15, 2021 02:02:05 PM CDT
Modified By:
- IceCube Upgrade Winter r/MoniPowe toring Requirements Rev 12.16.2020 Purpose: This document is to inform ASC of IceCube Upgrade’s (A‐334) requirements for heating and monitoring equipment during the South Pole winter. - Contents: 1. - Executive Summary 2. - Container Heating Requirements 3. - Hose Reel Heating Requirements 4. - Monitoring Requirements 5. Fuel Requirements 1. Executive Summary IceCube Upgrade requires the following for the duration of the South Pole winter: ‐ 39.6kW of 480V 3 phase power (at peak load) ‐ 10.5kW of 208V 3 phase power (at peak load) ‐ Remote monitoring via wireless or Eth...